Setup Process
1. Navigate to the
CALIBRATION
menu, and scroll to the
MOTOR PARAM
option. The starting
display will be:
C A L I B R A T I O N
M O T O R P A R A M
2. Press the ENTER key
8 5
< 1 8 0 0 >
3. Use UP and DOWN arrows to adjust value as required, then press the ENTER key
8 6
< 1 . 2 >
4. Use UP and DOWN arrows to adjust value as required, then press the ENTER key
8 7
< 2 3 0 >
5. Use UP and DOWN arrows to adjust value as required, then press the ENTER key
8 8
< 6 0 >
6. Use UP and DOWN arrows to adjust value as required, then press the ENTER key
9 1
< 0 . 8 0 >
7. Use UP and DOWN arrows to adjust value as required, then press the ENTER key
8 1
E N T E R T O S T A R T
8. Press the ENTER key
C A L I B R A T I N G
9. The last screen will show
M O T O R P A R A M
c a l i b r a t e d
10. Upon completion of the routine, remove power from the MPC VECTOR controller for one minute,
and then re-apply power to complete the process.
After all of the Parameters have been entered, the drive needs to perform an auto-calibration routine
(Parameter 81). This calibration routine will take several seconds to complete. The user may use the Menu
Key to back up and/or out of the calibration any time prior to the auto calibration. The motor, and therefore
the pump, will not run during this auto-calibration procedure.