23
9. Press the UP and/or DOWN arrow keys to adjust the Max Current setpoint.
M A X S E T P T 2 0 . 0 M A
F L O W : 4 . 0 0 G P M
10. Press ENTER to accept the Current Setpoint. The cursor will blink on the bottom line indicating that the
Flow setpoint may be adjusted.
11. Press the UP and/or DOWN arrow keys to adjust the Max Flow setpoint. Note that you can not set this
value greater than the Maximum Flow the pump is rated for (you may see the maximum rated flow in the
Pump Information screens).
M A X S E T P T 2 0 . 0 M A
F L O W : 5 . 9 2 G P M
You may back out of the DRY calibration routine at any point up to now without saving any calibration
settings. Use the MENU button to back up.
12. Press the ENTER key to save the new Analog Calibration values. Upon completion of Calibration
you should see the following screen.
P U M P F L O W
C A L I B R A T E D
13. Press the MENU key several times to return to Operations Mode.
To optimize feedback, it is best to set 4mA to 0 flow and 20mA to a value slightly higher (10-20% or
so) than your max desired flow setting. This allows the user a full range of flow setpoints as well as
giving the MPC VECTOR the best possible Analog resolution.