13. FIELD WIRING SUMMARY
Connector Location
Function/Connection
Reference
Section
J7
Line
Line connection 115VAC, Line 1 connection 230
VAC
Electrical
Wiring
Neutral
Neutral connection 115 VAC, Line 2 connection 230
VAC
Electrical
Wiring
Ground
Earth ground connection 115 or 230 VAC
Electrical
Wiring
J4
Position 1
Analog input (control) signal positive (+) Analog Input
(current loop)
Position 2
Analog input (control) signal common (-) Analog Input
(current loop)
Position 3
Analog output (feedback) signal positive (+) Analog Output
(current loop)
Position 4
Analog output (feedback) signal common (-) Analog Output
(current loop)
Position 5
Motor enable dry contact Motor Status
Input
Position 6
Motor enable dry contact Motor Status
Input